Steel pipe |
HDPE casing pipe |
||||||
DN |
Outer pipe diameter |
STANDARD |
PLUS |
2xPLUS |
Service valve diameter |
HDPE casing pipe |
||
|
dz [mm] |
Dz [mm] |
Dz [mm] |
Dz [mm] |
DN |
Dz2 [mm] |
||
32 |
42,4 |
110 |
125 |
140 |
25 |
110 |
||
40 |
48,3 |
110 |
125 |
140 |
25 |
110 |
||
50 |
60,3 |
125 |
140 |
160 |
25 |
110 |
||
65 |
76,1 |
140 |
160 |
180 |
32 |
125 |
||
80 |
88,9 |
160 |
180 |
200 |
32 |
125 |
||
100 |
114,3 |
200 |
225 |
250 |
32 |
125 |
||
125 |
139,7 |
225 |
250 |
280 |
40 |
125 |
||
150 |
168,3 |
250 |
280 |
315 |
40 |
125 |
||
200 |
219,1 |
315 |
355 |
400 |
50 |
140 |
||
250 |
273,0 |
400 |
450 |
500 |
50 |
140 |
||
300 |
323,9 |
450 |
500 |
560 |
50 |
140 |
||
350 |
355,6 |
500 |
560 |
630 |
65 |
160 |
||
400 |
406,4 |
560 |
630 |
710 |
65 |
160 |
||
450 |
457,0 |
630 |
710 |
– |
65 |
160 |
||
500 |
508,0 |
710 |
800 |
– |
100 |
225 |
||
600 |
610,0 |
800 |
900 |
– |
100 |
225 |
||
700 |
711,0 |
900 |
1000 |
– |
100 |
225 |
Comments:
Valves with stainless steel body
Ball valves on the drainage pipeline DN25÷DN100.
Hmin=0.5×(Dz1+Dz)+70 [mm].
L2=1000+Dz1+A [mm].
A – determine from the heating network design.
Recommended A for main pipe diameters:
DN32÷DN150 A≥140 mm,
DN200÷DN700 A≥200 mm.
Other diameters on request.
Main pipeline 1.5 m long.
For longer drainage systems, a tee should be used together with a pre-insulated pipe with a service valve.
Diameters and wall thicknesses not included in the table – on request.